Grounding Transformers - Electrical Design, Transformer Design, and Distribution Transformer Design

Grounding is clearly one of the most importantHow to Specify a Grounding Transformer
aspects of electrical design, but it steadfastlyThe basic parameters required for quoting a
continues to be misinterpreted and misunderstood.grounding transformer are:
Millions of dollars in liability and loss can be- Primary Voltage - This is the system voltage to
attributed to ground-fault arcing; thus,which the grounded winding is to be connected.
grounding-related issues should top the checklistsDon't forget to specify the BIL also. In some
of any electrical contractor.cases the BIL will be dictated by equipment
Grounding Transformers:considerations, such as 150 kV BIL ratings on
Simply put, a grounding transformer is used to34500 volt wind farms because of the limitation
provide a ground path to either an ungroundedon dead front connectors.
"Y" or a delta connected system. Grounding- Rated KVA - Because the grounding
transformers are typically used to:transformer is normally a short time device, its
size and cost are less when compared with a
1. Provide a relatively low impedance path tocontinuous duty transformer of equal kVA rating.
ground, thereby maintaining the system neutral atFor this reason, grounding transformers are often
or near ground potentialnot sized by "kVA" but by their continuous and
2. Limit the magnitude of transient over voltagesshort time current ratings. Regardless of how you
when re-striking ground faults occurrate it, the grounding transformer must be sized
3. Provide a source of ground fault current duringto carry the rated continuous primary phase
line-to-ground faultscurrent without exceeding its temperature limit.
4. Permit the connection of phase to neutral loadsThis load includes the magnetizing current of the
when desiredcore, the capacitive charging current for the
If a single line-to-ground fault occurs on ancables, and any auxiliary load if applicable. The
ungrounded or isolated system, no return pathhigher this value, the larger and more costly the
exists for the fault current, thus no current flows.transformer will be. Typical continuous current
The system will continue to operate but the othervalues can be as low as 5 amps to as high as a
two un-faulted lines will rise in voltage by thefew hundred. Be sure to include any auxiliary
square root of 3, resulting in overstressing of theloading requirements.
transformer insulation and other associated- Continuous Neutral Current - The continuous
components on the system by 173%. MOVneutral current is defined as three times the
lightning arresters are particularly susceptible tophase to current, or in other words, the zero
damage from heating by leakage across thesequence current. This is usually considered to be
blocks even if the voltage increase is notzero if the system is balanced. However, for the
sufficient to flash over. A grounding transformerpurposes of designing a grounding transformer, it
provides a ground path to prevent this.is a value that is expected to flow in the neutral
Large multi-turbine wind farms provide ancircuit without tripping protective circuits (which
example of the use of grounding transformerswould force the current to be zero) or the
for fault protection on ungrounded lines. In manyleakage current to ground that is not a
wind farms the substation transformer providessymmetrical function. Again this value is needed to
the sole ground source for the distributiondesign for thermal capacity of the grounding
system. When a ground fault on a collector cabletransformer.
causes the substation circuit breaker for that- Fault current and duration - This value is needed
cable to open, the wind turbine string becomesto calculate the short time heating that results
isolated from the ground source.from a fault on the system and should be
The turbines do not always detect this fault ordetermined from an engineered system study.
the fact that the string is isolated and ungrounded;Typical values for this range from a few hundred
thus the generators continue to energize theamps to a few thousand amps with duration
collector cable, and the voltages between thetimes expressed in seconds and not cycles. For
un-faulted cables and the ground rise far aboveinstance, a value of 400 amps for 10 seconds is
the normal voltage magnitude as described above.typical. The fault duration is a critical parameter
A grounding transformer placed on the turbinefor the transformer designer. Where protection
string provides a ground path in the event theschemes use the grounding transformer for
string becomes isolated from the system ground.tripping functions, a relatively short time duration
Construction:is specified (5 -10 seconds). On the other hand, a
Grounding transformers are normally constructedcontinuous or extended neutral fault current
either withduration would be required when the grounding
transformer is used in a ground fault alarm
1. A ZigZag (Zn) connected winding with orscheme.
without an auxiliary winding or- Impedance - The impedance can be expressed
2. As a Wye (Ynd) connected winding with a deltaas a percentage or as an ohm value per phase. In
connected secondary that may or may not beeither case it should be chosen so that the
used to supply auxiliary powerun-faulted phase voltages during a ground fault
The geometry of the Zig-Zag connection is usefulare within the temporary over-voltage capability
to limit circulation of third harmonics and can beof the transformer and associated equipment,
used without a Delta connected winding or the 4-such as arresters and terminal connectors.
or 5-leg core design normally used for thisBecause of this description, the values can vary
purpose in distribution and power transformers.from as low as 8% to almost 100%. This value
Eliminating the need for a secondary winding canmust come from the system designer.
make this option both less expensive and smaller- Primary winding connection - Specify the type
than a comparable two-winding groundingof primary connection, either Zig-Zag or grounded
transformer. Furthermore, use of a Zig-ZagWye.
transformer provides grounding with a smaller unit- Secondary connection - specify the secondary
than a two-winding Wye-Delta transformervoltage and connection when applicable. Specify
providing the same zero sequence impedance.the size of auxiliary loading to be connected for
Wye connected grounding transformers, on theeither Zn or Wye connected primary windings. If
other hand, require either a delta connectedthe option is to have a two winding transformer
secondary or the application of 4 or 5 leg corewith no secondary load, advise if the delta winding
construction to provide a return flux path forcan be "buried" (that is not brought out) or if only
unbalanced loading associated with this primaryone bushing is to be brought out for grounding to
connection. Since it is often desirable to providethe tank or testing.
auxiliary power from the grounding transformer· Basic overall construction features -
secondary winding, this benefit can sway the endnote the following features as they apply to each
user to specify a two-winding groundingtransformer
transformer in lieu of a Zig-Zag connection. The· Compartmental Padmount transformer
current trend in wind farm designs is toward thewith integral tamperproof compartment or
Wye connected primary with a delta secondary.substation design
It is important to understand that both Zig-Zag· Outdoor or indoor
and two-winding grounding transformers can be· Fluid type- mineral oil, silicone,
provided with the ability to provide auxiliaryEnvirotemp FR3
power, and this can be either a Wye or Delta· Connectivity -dead front, live front,
connected load.spade terminals, location of terminals - cover or
A solidly grounded system using a groundingsidewall , exposed or enclosed, etc
transformer offers many safety improvements· Temperature rise is assumed to be 65'C
over an ungrounded system. However, the· Site elevation or environmental concerns
ground transformer alone lacks the current limiting· Special paint as required
ability of a resistive grounding system. For this· Neutral Ground Resistors - The rated
reason, neutral ground resistors are often used involtage of the NGR should be equal to the line to
conjunction with the grounding transformer to limitground voltage of the grounding transformer. The
neutral ground fault current magnitude. Their ohmcurrent rating and duration should match the
values should be specified to allow high enoughgrounding transformer ratings. Remember to set
ground fault current flow to permit reliablethe current rating high enough to be above the
operation of the protective relaying equipment,cable charging current and grounding transformer
but low enough to limit thermal damage.magnetizing current.